Model No: 12KW+32KWh
12KW/32KWh All-in-one Energer Storage System
Quantity :
DATA SHEET
Elevate Your Energy. Solenux
ModelESS LV 12KW+32KWH
| AC Input | |
|---|---|
| Rated Input Voltage (VAC) | 400V/3L+N+PE |
| Voltage Range (VAC) | 400V/-20%~15% |
| Frequency (Hz) | 50/60 (Auto Adaptive) |
| AC Output | |
| Rated Capacity (W) | 15KVA |
| Surge Power (VA) | 18KVA |
| Voltage (VAC) | 400V/-20%~15% |
| Power Factor (PF) | 1 |
| Frequency | 50/60Hz±0.1% |
| Switch Time (ms) | 10 |
| Wave Form | Pure Sine Wave |
| Overload Protection | 60s@102%~110%; 10s@110%~130%; 3s@130%~150%; 0.2s@>150% |
| Max. Efficiency (Battery Mode) | 93%@48VDC |
| Charger (PV/AC) | |
| Solar Charger Type | MPPT |
| Max PV Input Current/Power | 9000W+9000W |
| Operating Voltage Range (VDC) | 80-520 |
| Max. PV Open Circuit Voltage (VDC) | 500 |
| Max. PV Charge Current (A) | 200A |
| Max. AC Charge Current (A) | 160A |
| Max. Charge Current (PV+AC) (A) | 200A |
| Battery | |
| Nominal Battery Voltage | 51.2VDC |
| Rated Energy | 64KWh (0.5C, 25℃) |
| Usable Energy (90%DOD) | 57.6KWh |
| Max. Charge/Discharge Current | 400A/400A |
| Operation Voltage Range | 40.5Vdc ~ 58.4Vdc |
| Operation Temperature | -10℃~+50℃ |
| Interface | |
| Reveal | LCD |
| Communication | USB |
| Monitoring | WiFi |
| General Data | |
| Ingress Protection | IP20 |
| Operating Temperature | -10℃~50℃ |
| Relative Humidity | 5% ~ 95% (Non-condensing) |
| Storage Temperature | -15℃~60℃ |
| Max. Operating Altitude | 4000m (Derating above 1000m) |
| Dimension | |
| LxWxH (products size) | Inverter: 745*440*76mm / Battery: 745*440*240mm (1pcs) |